Vulnerability in Siemens Industrial Edge Management Pro V1
CVE-2026-33892
A vulnerability has been identified in Industrial Edge Management Pro V1 (All versions >= V1.7.6 < V1.15.17), Industrial Edge Management Pro V2 (All versions >= V2.0.0 < V2.1.1), Industrial Edge Management Virtual (All versions >= V2.2.0 < V2.8.0). Affected management systems do not properly enforce user authentication on remote connections to devices. This could facilitate an unauthenticated remote attacker to circumvent authentication and impersonate a legitimate user. Successful exploitation requires that the attacker has identified the header and port used for remote connections to devices and that the remote connection feature is enabled for the device. Exploitation allows the attacker to tunnel to the device. Security features on this device itself (e.g. app specific authentication) are not affected.
EPSS: 0.002 (11.3th percentile) — read the EPSS interpretation.
CVSS v3 metric
CVSS v3 base score 7.1 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L.
Affected products
- Siemens Industrial Edge Management Pro V1 — versions V1.7.6
- Siemens Industrial Edge Management Pro V2 — versions V2.0.0
- Siemens Industrial Edge Management Virtual — versions V2.2.0
Weakness classification (CWE)
References
Frequently asked questions
- What is CVE-2026-33892?
- CVE-2026-33892 is a high-severity vulnerability in Siemens Industrial Edge Management Pro V1, classified under Authentication Bypass by Primary Weakness. CVSS score: 7.1/10. Published 2026-04-14.
- How severe is CVE-2026-33892?
- High severity. CVSS v3 base score is 7.1 out of 10.