Buffer overflow in Openplcproject Openplc V3

CVE-2026-11826

OpenPLC_v3 contains a heap-based buffer overflow in the getData() function in webserver/core/modbus_master.cpp. getData() reads characters between two delimiters into a caller-supplied buffer with no size parameter and no bounds check. In parseConfig() the function is invoked with the 100-byte heap-allocated MB_device.dev_name field. An authenticated attacker with access to the OpenPLC web interface can send a crafted HTTP POST to the /modbus endpoint with an oversized device_name value; the value is persisted to mbconfig.cfg and parsed on load, overflowing dev_name and overwriting adjacent struct fields (protocol at offset 108, dev_address at offset 109, ip_port at offset 210). A 200-byte payload writes 100 bytes past the allocation. The result is heap corruption leading to runtime crash and denial of service of the PLC process control loop, with attacker-controlled overwrite of adjacent configuration fields. The upstream repository was archived on 2026-04-04 and no fix is expected; the vendor has confirmed the issue does not affect OpenPLC Runtime v4.

Vulnerability class: Buffer Overflow

EPSS: 0.007 (52.5th percentile) — read the EPSS interpretation.

CVSS v3 metric

CVSS v3 base score 8.8 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H.

Affected products

Weakness classification (CWE)

References

Frequently asked questions

What is CVE-2026-11826?
CVE-2026-11826 is a high-severity vulnerability in Openplcproject Openplc V3, classified under Heap-based Buffer Overflow. CVSS score: 8.8/10. Published 2026-07-18.
How severe is CVE-2026-11826?
High severity. CVSS v3 base score is 8.8 out of 10.