Vulnerability in Siemens Apogee Pxc+talon Tc Series (Bacnet)
CVE-2025-40555
- CVSS v3
- 4.7 Medium
- Public exploits
- None known
- EPSS
- 0.002 · 12.5th percentile
- Published
- 2025-05-13
A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 4.7 (Medium). Vector: CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:L.
EPSS exploit prediction
EPSS 0.002, 12.5th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Apogee Pxc+talon Tc Series (Bacnet) — versions 0