Vulnerability in Siemens Telecontrol Server Basic

CVE-2025-29931

A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected product does not properly validate a length field in a serialized message which it uses to determine the amount of memory to be allocated for deserialization. This could allow an unauthenticated remote attacker to cause the application to allocate exhaustive amounts of memory and subsequently create a partial denial of service condition.
Successful exploitation is only possible in redundant Telecontrol Server Basic setups and only if the connection between the redundant servers has been disrupted.

Published · last modified .

CVSS v3 metric

CVSS v3 base score 3.7 (Low). Vector: CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:L.

EPSS exploit prediction

EPSS 0.005, 39.8th percentile (scored ); unchanged over 30 days. About EPSS.

Affected products

Weakness classification (CWE)

Public exploits and proof-of-concept code

Also mentioned in 2 other repositories (fkie-cad/nvd-json-data-feeds, JsHuang/CVE-Assigned). These reference the CVE in a list, notes or a scanner and are not exploit code for it.

References