RCE in Siemens Ozw672
CVE-2025-26389
A vulnerability has been identified in OZW672 (All versions < V8.0), OZW772 (All versions < V8.0). The web service in affected devices does not sanitize the input parameters required for the `exportDiagramPage` endpoint. This could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.
Vulnerability class: Command Injection (OS Command Injection)
Published · last modified .
CVSS v3 metric
CVSS v3 base score 10.0 (Critical). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H.
EPSS exploit prediction
EPSS 0.010, 63.3th percentile (scored ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Ozw672 — versions 0
- Siemens Ozw672 Firmware
- Siemens Ozw772 — versions 0
- Siemens Ozw772 Firmware
Weakness classification (CWE)
References
- cert-portal.siemens.com/productcert/html/ssa-047424.html (Vendor Advisory)