Integer overflow in Honeywell C200e

CVE-2025-2523

The Honeywell Experion PKS

and OneWireless WDM

contains an Integer Underflow

vulnerability

in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which could result in a failure during subtraction allowing remote code execution.

Honeywell recommends updating to the most recent version of

Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1.

The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.

Published · last modified .

CVSS v3 metric

CVSS v3 base score 9.4 (Critical). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H.

EPSS exploit prediction

EPSS 0.008, 56.8th percentile (scored ); unchanged over 30 days. About EPSS.

Affected products

Weakness classification (CWE)

References