Vulnerability in Boschrexroth Ctrlx Hmi Web Panel Wr2107
CVE-2023-45321
The Android Client application, when enrolled with the define method 1 (the user manually inserts the server ip address), use HTTP protocol to retrieve sensitive information (ip address and credentials to connect to a remote MQTT broker entity) instead of HTTPS and this feature is not configurable by the user. Due to the lack of encryption of HTTP,this issue allows an attacker placed in the same subnet network of the HMI device to intercept username and password necessary to authenticate to the MQTT server responsible to implement the remote management protocol.
EPSS: 0.001 (2.5th percentile) — read the EPSS interpretation.
CVSS v3 metric
CVSS v3 base score 8.3 (High). Vector: CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L.
Affected products
- Boschrexroth Ctrlx_hmi_web_panel_wr2107
- Boschrexroth Ctrlx_hmi_web_panel_wr2107_firmware
- Boschrexroth Ctrlx_hmi_web_panel_wr2110
- Boschrexroth Ctrlx_hmi_web_panel_wr2110_firmware
- Boschrexroth Ctrlx_hmi_web_panel_wr2115
- Boschrexroth Ctrlx_hmi_web_panel_wr2115_firmware
- Bosch Rexroth Ag Ctrlx Hmi Web Panel - Wr21 (Wr2107) — versions all
- Bosch Rexroth Ag Ctrlx Hmi Web Panel - Wr21 (Wr2110) — versions all
- Bosch Rexroth Ag Ctrlx Hmi Web Panel - Wr21 (Wr2115) — versions all
Weakness classification (CWE)
References
- psirt@bosch.com (vendor-advisory, Mitigation, Vendor Advisory)
Frequently asked questions
- What is CVE-2023-45321?
- CVE-2023-45321 is a high-severity vulnerability in Boschrexroth Ctrlx Hmi Web Panel Wr2107, classified under Cleartext Transmission of Sensitive Information. CVSS score: 8.3/10. Published 2023-10-25.
- How severe is CVE-2023-45321?
- High severity. CVSS v3 base score is 8.3 out of 10.