Vulnerability in Siemens Cp-8031 Master Module
CVE-2023-42797
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.20), CP-8050 MASTER MODULE (All versions < CPCI85 V05.20). The network configuration service of affected devices contains a flaw in the conversion of ipv4 addresses that could lead to an uninitialized variable being used in succeeding validation steps.
By uploading specially crafted network configuration, an authenticated remote attacker could be able to inject commands that are executed on the device with root privileges during device startup.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 6.6 (Medium). Vector: CVSS:3.1/AV:N/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:H.
EPSS exploit prediction
EPSS 0.005, 46.4th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Cp-8031 Master Module — versions All versions < CPCI85 V05.20
- Siemens Cp-8050 Master Module — versions All versions < CPCI85 V05.20
- Siemens Sicam A8000 Cp-8031 Firmware
- Siemens Sicam A8000 Cp-8050 Firmware
Weakness classification (CWE)
References
- cert-portal.siemens.com/productcert/pdf/ssa-583634.pdf (Patch, Vendor Advisory)