RCE in Siemens Cp-8031 Firmware
CVE-2023-28489
- CVSS v3
- 9.8 Critical
- Public exploits
- None known
- EPSS
- 0.028 · 86.9th percentile
- Published
- 2023-04-11
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter “Remote Operation” is enabled. The parameter is disabled by default.
The vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.
Vulnerability class: Command Injection (OS Command Injection)
Published · last modified .
CVSS v3 metric
CVSS v3 base score 9.8 (Critical). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H.
- Attack Vector
- Network
AV:N - Attack Complexity
- Low
AC:L - Privileges Required
- None
PR:N - User Interaction
- None
UI:N - Scope
- Unchanged
S:U - Confidentiality
- High
C:H - Integrity
- High
I:H - Availability
- High
A:H
EPSS exploit prediction
EPSS 0.028, 86.9th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Cp-8031 Firmware
- Siemens Cp-8031 Master Module — versions All versions < CPCI85 V05
- Siemens Cp-8050 Firmware
- Siemens Cp-8050 Master Module — versions All versions < CPCI85 V05