Vulnerability in Schneider Electric Custom Reports (Rms16.dll)
CVE-2023-27982
A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists in the Data Server that could cause manipulation of dashboard files in the IGSS project report directory, when an attacker sends specific crafted messages to the Data Server TCP port, this could lead to remote code execution when a victim eventually opens a malicious dashboard file. Affected Products: IGSS Data Server(IGSSdataServer.exe)(V16.0.0.23040 and prior), IGSS Dashboard(DashBoard.exe)(V16.0.0.23040 and prior), Custom Reports(RMS16.dll)(V16.0.0.23040 and prior).
Published · last modified .
CVSS v3 metric
CVSS v3 base score 8.8 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H.
EPSS exploit prediction
EPSS: 0.004 (32.0th percentile), scored .
Very low probability of exploitation in the next 30 days; routine patching cadence is appropriate. 32nd percentile — 32.0% of CVEs in the catalogue have a lower EPSS than this one. How to read EPSS.
EPSS over last 30 days · oldest: 0.004 · newest: 0.004 · change: 0.000
Affected products
Weakness classification (CWE)
References
- download.schneider-electric.com/files (Patch, Vendor Advisory)
Frequently asked questions
- What is CVE-2023-27982?
- CVE-2023-27982 is a high-severity vulnerability in Schneider Electric Custom Reports (Rms16.dll), classified under Insufficient Verification of Data Authenticity. CVSS score: 8.8/10. Published 2023-03-21.
- How severe is CVE-2023-27982?
- High severity. CVSS v3 base score is 8.8 out of 10.