Vulnerability in Hitachi Energy Relion 670/650/sam600-Io Series
CVE-2022-3864
A vulnerability exists in the Relion update package signature validation. A tampered update package could cause the IED to restart. After restart the device is back to normal operation.
An attacker could exploit the vulnerability by first gaining access to
the system with security privileges and attempt to update the IED
with a malicious update package. Successful exploitation of this
vulnerability will cause the IED to restart, causing a temporary Denial of Service.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 4.5 (Medium). Vector: CVSS:3.1/AV:N/AC:L/PR:H/UI:R/S:U/C:N/I:N/A:H.
EPSS exploit prediction
EPSS 0.004, 29.4th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Hitachi Energy Relion 670/650/sam600-Io Series — versions Relion 670/650 series version 2.2.0 all revisions, Relion 670/650/SAM600-IO series version 2.2.1 all revisions, Relion 670 series version 2.2.2 all revisions
- Hitachienergy Relion 650 Firmware — versions 2.2.0, 2.2.1, 2.2.4
- Hitachienergy Relion 670 Firmware — versions 2.2.0, 2.2.1, 2.2.2
- Hitachienergy Relion Sam600-Io Firmware — versions 2.2.1
Weakness classification (CWE)
References
- publisher.hitachienergy.com/preview (Vendor Advisory)