Vulnerability in Powertekpdus Basic Pdu
CVE-2022-33175
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 9.8 (Critical). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H.
EPSS exploit prediction
EPSS: 0.017 (76.5th percentile), scored .
Low probability of exploitation in the next 30 days, but still tracked. 76th percentile — 76.5% of CVEs in the catalogue have a lower EPSS than this one. How to read EPSS.
EPSS over last 30 days · oldest: 0.017 · newest: 0.017 · change: 0.000
Affected products
Weakness classification (CWE)
Public proof-of-concept exploits
References
- gynvael.coldwind.pl/ (Exploit, Third Party Advisory)
Frequently asked questions
- What is CVE-2022-33175?
- CVE-2022-33175 is a critical-severity vulnerability in Powertekpdus Basic Pdu, classified under Incorrect Permission Assignment for Critical Resource. CVSS score: 9.8/10. Published 2022-06-13.
- How severe is CVE-2022-33175?
- Critical severity. CVSS v3 base score is 9.8 out of 10.
- Is CVE-2022-33175 known to be exploited?
- 2 public proof-of-concept repositories are indexed. Not currently listed in the CISA KEV catalog.