Vulnerability in Honeywell Saia Pg5 Controls Suite
CVE-2022-30319
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 8.1 (High). Vector: CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N.
EPSS exploit prediction
EPSS 0.007, 53.9th percentile (scored ); unchanged over 30 days. About EPSS.
Affected products
Weakness classification (CWE)
References
- www.forescout.com/blog/ (Third Party Advisory)
- www.cisa.gov/uscert/ics/advisories/icsa-22-207-03 (US Government Resource, Third Party Advisory)