Vulnerability in Abb Rtu500 Firmware
CVE-2022-28613
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 7.5 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.
EPSS exploit prediction
EPSS 0.010, 63.1th percentile (scored ); unchanged over 30 days. About EPSS.
Affected products
- Abb Rtu500 Firmware
- Hitachi Energy Rtu500 Series Cmu Firmware — versions 12.0.*, 12.2.*, 12.4.*
- Hitachienergy Rtu500 Firmware
Weakness classification (CWE)
References
- publisher.hitachienergy.com/preview (vendor-advisory)
- search.abb.com/library/Download.aspx