Vulnerability in Ls-Electric Gm7 Firmware

CVE-2022-2758

Passwords are not adequately encrypted during the communication process between all versions of LS Industrial Systems (LSIS) Co. Ltd LS Electric XG5000 software prior to V4.0 and LS Electric PLCs: all versions of XGK-CPUU/H/A/S/E prior to V3.50, all versions of XGI-CPUU/UD/H/S/E prior to V3.20, all versions of XGR-CPUH prior to V1.80, all versions of XGB-XBMS prior to V3.00, all versions of XGB-XBCH prior to V1.90, and all versions of XGB-XECH prior to V1.30. This would allow an attacker to identify and decrypt the password of the affected PLCs by sniffing the PLC’s communication traffic.

Published · last modified .

CVSS v3 metric

CVSS v3 base score 6.5 (Medium). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N.

EPSS exploit prediction

EPSS 0.004, 35.2th percentile (last changed ); unchanged over 30 days. About EPSS.

Affected products

Weakness classification (CWE)

References