Improper input validation in Hitachi Energy Rtu500 Series
CVE-2022-2502
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 7.5 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.
EPSS exploit prediction
EPSS 0.006, 51.5th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Hitachi Energy Rtu500 Series — versions RTU500 series CMU Firmware version 13.3.1, RTU500 series CMU Firmware version 13.3.2, RTU500 series CMU Firmware version 13.3.3
- Hitachienergy Rtu500 Firmware — versions 13.3.1, 13.3.2, 13.3.3
Weakness classification (CWE)
References
- publisher.hitachienergy.com/preview (vendor-advisory)
- search.abb.com/library/Download.aspx