Resource exhaustion in Schneider-Electric Modicon M340 Bmxp341000
CVE-2022-22724
A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC. Affected Product: Modicon M340 CPUs: BMXP34 (All Versions)
Vulnerability class: DoS (Denial of Service)
Published · last modified .
CVSS v3 metric
CVSS v3 base score 7.5 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.
EPSS exploit prediction
EPSS: 0.009 (59.1th percentile), scored .
Very low probability of exploitation in the next 30 days; routine patching cadence is appropriate. 59th percentile — 59.1% of CVEs in the catalogue have a lower EPSS than this one. How to read EPSS.
EPSS over last 30 days · oldest: 0.009 · newest: 0.009 · change: 0.000
Affected products
- Schneider-Electric Modicon M340 Bmxp341000
- Schneider-Electric Modicon M340 Bmxp341000 Firmware
- Schneider-Electric Modicon M340 Bmxp342000
- Schneider-Electric Modicon M340 Bmxp342000 Firmware
- Schneider-Electric Modicon M340 Bmxp342010
- Schneider-Electric Modicon M340 Bmxp3420102
- Schneider-Electric Modicon M340 Bmxp3420102 Firmware
- Schneider-Electric Modicon M340 Bmxp342010 Firmware
- Schneider-Electric Modicon M340 Bmxp342030
- Schneider-Electric Modicon M340 Bmxp3420302
Weakness classification (CWE)
References
- download.schneider-electric.com/files (Patch, Mitigation, Vendor Advisory)
Frequently asked questions
- What is CVE-2022-22724?
- CVE-2022-22724 is a high-severity vulnerability in Schneider-Electric Modicon M340 Bmxp341000, classified under Uncontrolled Resource Consumption. CVSS score: 7.5/10. Published 2022-02-04.
- How severe is CVE-2022-22724?
- High severity. CVSS v3 base score is 7.5 out of 10.