CVE Explore

Improper input validation in Hitachi Energy Rtu500 Series

CVE-2021-35533

CVSS v3
7.5 High
Public exploits
None known
EPSS
0.009 · 61.8th percentile
Published
2021-11-26

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

Published · last modified .

CVSS v3 metric

CVSS v3 base score 7.5 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.

Attack Vector
Network AV:N
Attack Complexity
Low AC:L
Privileges Required
None PR:N
User Interaction
None UI:N
Scope
Unchanged S:U
Confidentiality
None C:N
Integrity
None I:N
Availability
High A:H

EPSS exploit prediction

EPSS 0.009, 61.8th percentile (last changed ); unchanged over 30 days. About EPSS.

Affected products

Weakness classification (CWE)

References