XSS in Siemens Climatix Pol908 (Bacnet/ip Module)
CVE-2020-7575
- CVSS v3
- 6.1 Medium
- Public exploits
- None known
- EPSS
- 0.007 · 52.2th percentile
- Published
- 2020-04-14
A vulnerability has been identified in Climatix POL908 (BACnet/IP module) (All versions), Climatix POL909 (AWM module) (All versions < V11.32). A persistent cross-site scripting (XSS) vulnerability exists in the web server access log page of the affected devices that could allow an attacker to inject arbitrary JavaScript code via specially crafted GET requests. The code could be potentially executed later by another (privileged) user. The security vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires no system privileges. An attacker could use the vulnerability to compromise the confidentiality and integrity of other users' web sessions.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 6.1 (Medium). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N.
- Attack Vector
- Network
AV:N - Attack Complexity
- Low
AC:L - Privileges Required
- None
PR:N - User Interaction
- Required
UI:R - Scope
- Changed
S:C - Confidentiality
- Low
C:L - Integrity
- Low
I:L - Availability
- None
A:N
EPSS exploit prediction
EPSS 0.007, 52.2th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Climatix Pol908 (Bacnet/ip Module) — versions All versions
- Siemens Climatix Pol908 Firmware
- Siemens Climatix Pol909 (Awm Module) — versions All versions < V11.32
- Siemens Climatix Pol909 Firmware
Weakness classification (CWE)
References
- cert-portal.siemens.com/productcert/pdf/ssa-886514.pdf (Vendor Advisory)