Vulnerability in Schneider-Electric Modicon M340 Firmware
CVE-2019-6806
- CVSS v3
- 7.5 High
- Public exploits
- None known
- EPSS
- 0.023 · 83.6th percentile
- Published
- 2019-05-22
A CWE-200: Information Exposure vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause the disclosure of SNMP information when reading variables in the controller using Modbus.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 7.5 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N.
- Attack Vector
- Network
AV:N - Attack Complexity
- Low
AC:L - Privileges Required
- None
PR:N - User Interaction
- None
UI:N - Scope
- Unchanged
S:U - Confidentiality
- High
C:H - Integrity
- None
I:N - Availability
- None
A:N
EPSS exploit prediction
EPSS 0.023, 83.6th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Schneider-Electric Modicon M340 Firmware
- Schneider-Electric Modicon M580 Firmware
- Schneider-Electric Modicon Premium Firmware
- Schneider-Electric Modicon Quantum Firmware
- Modicon M580 M340 Quantum Premium — versions Modicon M580 Modicon M340 Modicon Quantum Modicon Premium
References
- www.schneider-electric.com/en/download/document/SEVD-2019-134-11/ (Mitigation, Vendor Advisory)
- www.talosintelligence.com/vulnerability_reports/TALOS-2019-0769 (Exploit, Third Party Advisory)