Buffer overflow in Siemens Logo\!8
CVE-2019-6571
A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). An attacker with network access to port 10005/tcp of the LOGO! device could cause a Denial-of-Service condition by sending specially crafted packets. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation of the security vulnerability compromises availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known.
Vulnerability class: Buffer Overflow
EPSS: 0.016 (73.3th percentile) — read the EPSS interpretation.
CVSS v3 metric
CVSS v3 base score 7.5 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.
Affected products
- Siemens Logo\!8
- Siemens Logo\!8_firmware
- Siemens Ag Logo!8 — versions 6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02, 6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx
Weakness classification (CWE)
References
- productcert@siemens.com (Patch, x_refsource_MISC, Vendor Advisory)
Frequently asked questions
- What is CVE-2019-6571?
- CVE-2019-6571 is a high-severity vulnerability in Siemens Logo\!8, classified under Improper Restriction of Operations within the Bounds of a Memory Buffer. CVSS score: 7.5/10. Published 2019-06-12.
- How severe is CVE-2019-6571?
- High severity. CVSS v3 base score is 7.5 out of 10.