Buffer overflow in Siemens Logo\!8 Firmware
CVE-2019-6571
- CVSS v3
- 7.5 High
- Public exploits
- None known
- EPSS
- 0.016 · 76.2th percentile
- Published
- 2019-06-12
A vulnerability has been identified in SIEMENS LOGO!8 (6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx), SIEMENS LOGO!8 (6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02). An attacker with network access to port 10005/tcp of the LOGO! device could cause a Denial-of-Service condition by sending specially crafted packets. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected service. No user interaction is required to exploit this security vulnerability. Successful exploitation of the security vulnerability compromises availability of the targeted system. At the time of advisory publication no public exploitation of this security vulnerability was known.
Vulnerability class: Buffer Overflow
Published · last modified .
CVSS v3 metric
CVSS v3 base score 7.5 (High). Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.
- Attack Vector
- Network
AV:N - Attack Complexity
- Low
AC:L - Privileges Required
- None
PR:N - User Interaction
- None
UI:N - Scope
- Unchanged
S:U - Confidentiality
- None
C:N - Integrity
- None
I:N - Availability
- High
A:H
EPSS exploit prediction
EPSS 0.016, 76.2th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Logo\!8 Firmware
- Siemens Ag Logo!8 — versions 6ED1052-xyy08-0BA0 FS:01 / Firmware version < V1.82.02, 6ED1052-xyyxx-0BA8 FS:01 to FS:06 / Firmware version V1.80.xx and V1.81.xx
Weakness classification (CWE)
References
- cert-portal.siemens.com/productcert/pdf/ssa-774850.pdf (Patch, Vendor Advisory)