Buffer overflow in Schneider Electric Triconex Tricon
CVE-2018-7522
In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states.
Vulnerability class: Buffer Overflow
Published · last modified .
CVSS v3 metric
CVSS v3 base score 6.7 (Medium). Vector: CVSS:3.0/AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H.
EPSS exploit prediction
EPSS 0.004, 36.5th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Schneider Electric Triconex Tricon — versions MP model 3008 firmware versions 10.0-10.4
- Schneider-Electric Triconex Tricon Mp 3008 Firmware
Weakness classification (CWE)
References
- www.schneider-electric.com/en/download/document/SEVD-2017-347-01/ (Vendor Advisory)
- ics-cert.us-cert.gov/advisories/ICSA-18-107-02 (US Government Resource, Third Party Advisory)
- www.securityfocus.com/bid/103947 (Third Party Advisory, VDB Entry, vdb-entry)