Vulnerability in Siemens Digsi 4 Firmware
CVE-2018-4858
- CVSS v3
- 7.8 High
- Public exploits
- None known
- EPSS
- 0.018 · 78.9th percentile
- Published
- 2018-07-09
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
Published · last modified .
CVSS v3 metric
CVSS v3 base score 7.8 (High). Vector: CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H.
- Attack Vector
- Local
AV:L - Attack Complexity
- Low
AC:L - Privileges Required
- None
PR:N - User Interaction
- Required
UI:R - Scope
- Unchanged
S:U - Confidentiality
- High
C:H - Integrity
- High
I:H - Availability
- High
A:H
EPSS exploit prediction
EPSS 0.018, 78.9th percentile (last changed ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Digsi 4 Firmware
- Siemens Digsi 5 Firmware
- Siemens Ec 61850 System Configurator Firmware
- Siemens Sicam Pas\/pqs
- Siemens Sicam Pq Analyzer Firmware
- Siemens Sicam Scc Firmware
- Siemens Ag Iec 61850 System Configurator, Digsi 5 (Affected As Configurator Is Incorporated), 4, Sicam Pas/pqs, Pq Analyzer, Scc — versions IEC 61850 system configurator : All versions < V5.80, DIGSI 5 (affected as IEC 61850 system configurator is incorporated) : All versions < V7.80, DIGSI 4 : All versions < V4.93
Weakness classification (CWE)
Public exploits and proof-of-concept code
Also mentioned in 1 other repository (fkie-cad/nvd-json-data-feeds). These reference the CVE in a list, notes or a scanner and are not exploit code for it.
References
- cert-portal.siemens.com/productcert/pdf/ssa-159860.pdf (Vendor Advisory)
- www.securityfocus.com/bid/105933 (Third Party Advisory, VDB Entry, vdb-entry)
- ics-cert.us-cert.gov/advisories/ICSA-18-317-01 (US Government Resource, Third Party Advisory)