Vulnerability in Automationdirect Stride-Managed Ethernet Switch Models

CVE-2016-9335

A hard-coded cryptographic key vulnerability was identified in Red Lion Controls Sixnet-Managed Industrial Switches running firmware Version 5.0.196 and Stride-Managed Ethernet Switches running firmware Version 5.0.190. Vulnerable versions of Stride-Managed Ethernet switches and Sixnet-Managed Industrial switches use hard-coded HTTP SSL/SSH keys for secure communication. Because these keys cannot be regenerated by users, all products use the same key. The attacker could disrupt communication or compromise the system. CVSS v3 base score: 10, CVSS vector string: (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). Red Lion Controls recommends updating to SLX firmware Version 5.3.174.

Published · last modified .

CVSS v3 metric

CVSS v3 base score 10.0 (Critical). Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H.

EPSS exploit prediction

EPSS: 0.016 (74.5th percentile), scored .

Low probability of exploitation in the next 30 days, but still tracked. 74th percentile — 74.5% of CVEs in the catalogue have a lower EPSS than this one. How to read EPSS.

EPSS trend (30 days)EPSS over the last 30 days for CVE-2016-9335: held from 0.016 to 0.016.

EPSS over last 30 days · oldest: 0.016 · newest: 0.016 · change: +0.000

Affected products

Weakness classification (CWE)

References

Frequently asked questions

What is CVE-2016-9335?
CVE-2016-9335 is a critical-severity vulnerability in Automationdirect Stride-Managed Ethernet Switch Models, classified under Use of Hard-coded Cryptographic Key. CVSS score: 10.0/10. Published 2018-05-09.
How severe is CVE-2016-9335?
Critical severity. CVSS v3 base score is 10.0 out of 10.