Auth bypass in Siemens En100 Ethernet Module
CVE-2016-7114
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.87; SIPROTEC 7UT686 : All versions < V 4.02; SIPROTEC 7SD686 : All versions < V 4.05; SIPROTEC 7SJ66 : All versions < V 4.30. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations. A legitimate user must be logged into the web interface for the attack to be successful.
Vulnerability class: Broken Authentication
Published · last modified .
CVSS v3 metric
CVSS v3 base score 8.8 (High). Vector: CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H.
EPSS exploit prediction
EPSS: 0.021 (81.1th percentile), scored .
Low probability of exploitation in the next 30 days, but still tracked. 81st percentile — 81.1% of CVEs in the catalogue have a lower EPSS than this one. How to read EPSS.
EPSS over last 30 days · oldest: 0.021 · newest: 0.021 · change: 0.000
Affected products
Weakness classification (CWE)
References
Frequently asked questions
- What is CVE-2016-7114?
- CVE-2016-7114 is a high-severity vulnerability in Siemens En100 Ethernet Module, classified under Improper Authentication. CVSS score: 8.8/10. Published 2016-09-06.
- How severe is CVE-2016-7114?
- High severity. CVSS v3 base score is 8.8 out of 10.