Information disclosure in Siemens Siprotec Firmware
CVE-2016-4785
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain a limited amount of device memory content if network access was obtained. This vulnerability only affects EN100 Ethernet module included in SIPROTEC4 and SIPROTEC Compact devices.
Vulnerability class: Information Disclosure
Published · last modified .
CVSS v3 metric
CVSS v3 base score 5.3 (Medium). Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N.
EPSS exploit prediction
EPSS 0.027, 86.0th percentile (scored ); unchanged over 30 days. About EPSS.
Affected products
- Siemens Siprotec Firmware — versions 4.26
Weakness classification (CWE)
References
- www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-547990.pdf (Vendor Advisory)
- ics-cert.us-cert.gov/advisories/ICSA-16-140-02 (US Government Resource, Third Party Advisory)
- www.siemens.com/cert/pool/cert/siemens_security_advisory_SSA-323211.pdf
- www.securityfocus.com/bid/90773 (vdb-entry)
- ics-cert.us-cert.gov/advisories/ICSA-17-187-03
- www.securityfocus.com/bid/99471 (vdb-entry)