Buffer overflow in Sielcosistemi Winlog Lite
CVE-2012-4353
Stack-based buffer overflow in RunTime.exe in Sielco Sistemi Winlog Pro SCADA before 2.07.17 and Winlog Lite SCADA before 2.07.17 allows remote attackers to execute arbitrary code via a crafted port-46824 TCP packet that triggers an incorrect file-open attempt by the _TCPIPS_BinOpenFileFP function, a different vulnerability than CVE-2012-3815. NOTE: some of these details are obtained from third party information.
Vulnerability class: Buffer Overflow
Published · last modified .
CVSS v2 metric
CVSS v2 base score 9.3 (High). Vector: AV:N/AC:M/Au:N/C:C/I:C/A:C. This CVE predates CVSS v3 and has no v3 score from NVD.
EPSS exploit prediction
EPSS: 0.247 (97.8th percentile), scored .
Moderate probability of exploitation in the next 30 days — watch for active exploitation reports. 98th percentile — 97.8% of CVEs in the catalogue have a lower EPSS than this one. How to read EPSS.
EPSS over last 30 days · oldest: 0.248 · newest: 0.247 · change: -0.001
Affected products
- Sielcosistemi Winlog Lite — versions 2.06.00, 2.06.03, 2.06.04
- Sielcosistemi Winlog Pro — versions 2.06.00, 2.06.03, 2.06.04
Weakness classification (CWE)
References
- aluigi.org/adv/winlog_2-adv.txt (Exploit)
- www.us-cert.gov/control_systems/pdf/ICSA-12-213-01.pdf (US Government Resource)
- secunia.com/advisories/49395 (Vendor Advisory, third-party-advisory)
- www.sielcosistemi.com/en/news/index.html (Patch)